Electric Motor Troubleshooting 1 Exam Prep
Free practice questions

Free C-303 Practice Questions

10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.

Start the free practice test → ★★★★★4.9/5 from 2,400+ candidates · No signup

These 10 free C-303 questions are organized by exam domain, so you can see how each part of the Electric Motor Troubleshooting 1 blueprint is tested. Reveal the answer and explanation under each question.

Domain 1: adhering to troubleshooting safety rules

Question 1

A qualified technician locks out a 480 V motor and follows a procedure requiring the voltage tester to be proved immediately before and after the absence-of-voltage check. The tester works on the proving unit before the check and indicates zero at every required motor test point. On the final proving check, it fails to respond. What do these results establish?

Show answer & explanation

Correct answer: D - Absence of voltage has not been established; repeat the procedure with a functioning tester.

Domain 3: component testing

Question 2

Tightening the fourth mounting bolt shifts a motor's shaft out of alignment with its pump. During the isolated inspection, three motor feet rest firmly on the base, while a visible gap lies beneath the fourth. Tightening its bolt pulls that foot down. Which correction should come before final alignment?

Show answer & explanation

Correct answer: A - Restore firm support beneath the foot before realigning the shafts.

Domain 4: using digital multimeters, clamp-on ammeters, and megohmmeter

Question 3

Megohmmeter test record for a 460 V motor circuit: connected circuit, failed; motor alone, 200 MΩ; cable and terminations, 0.8 MΩ. The sections were safely isolated and discharged, with the cable disconnected at both ends. The procedure requires 500 V DC for 60 seconds and at least 5 MΩ for each section. All readings were taken under those conditions. What action does this record support?

Show answer & explanation

Correct answer: C - Investigate and correct the cable or its terminations before repeating the required tests.

Domain 5: series/compound/shunt DC motors

Question 4

Two DC motors are isolated after field-circuit faults. Motor A has an open field winding in series with its armature. Motor B has an open shunt-field branch, and its parallel armature branch would remain energized when power is restored. Which pairing correctly predicts the consequences of restoring normal power before repair?

Show answer & explanation

Correct answer: A - A loses armature current; B can overspeed under a light load.

Question 5

A cumulative-compound DC motor is taken out of service after a reconnection test. It still turns in its original direction, but adding load now makes its speed rise abnormally. Armature supply voltage and shunt-field current stayed at their normal values. Which reconnection error best fits this change?

Show answer & explanation

Correct answer: A - The series field was reversed relative to the unchanged shunt field.

Domain 6: dual voltage/wye/delta 3-phase AC motors

Question 6

A three-phase induction motor continues rotating but becomes abnormally hot. Before it is safely stopped and isolated, a qualified technician measures each supply conductor individually with a verified clamp meter. The steady readings are 0 A, 14 A, and 14 A. Which investigation should take priority?

Show answer & explanation

Correct answer: B - Trace the missing phase through the supply and motor connections.

Question 7

Since being moved from a 460 V supply to a balanced 230 V supply, a nine-lead 230/460 V series/parallel induction motor cannot accelerate its usual load. Supply frequency remains at the motor's rating. Isolated inspection finds the leads still arranged according to the 460 V connection diagram. Which condition best explains the reduced starting torque?

Show answer & explanation

Correct answer: D - The coil sections remain in series and receive insufficient voltage.

Domain 7: capacitor start/permanent/start-run/split phase single-phase AC motors

Question 8

Both windings carry current as a capacitor-start, induction-run pump motor accelerates normally in a guarded test. At running speed, the starting contact opens and auxiliary-winding current falls to zero. The main winding continues carrying normal running current. How should the technician assess the starting circuit?

Show answer & explanation

Correct answer: C - Normal cutout leaves the main winding carrying running current.

Question 9

On a digital multimeter's resistance function, the reading rises to OL while testing the isolated, discharged run capacitor from a permanent split capacitor (PSC) blower motor with unreliable starting. The capacitor is disconnected from all parallel paths. A separate capacitance test places it within its marked tolerance. Which conclusion is supported?

Show answer & explanation

Correct answer: C - The charging response can be normal; continue isolating the starting fault.

Domain 8: measuring motor speed/torque/power

Question 10

During a guarded motor acceptance test, measured real electrical input is 8.0 kW, efficiency at that operating point is 90%, and shaft speed is 1,750 rpm. The procedure requires at least 42 N·m at this test point. Use torque (N·m) = 9550 × shaft power (kW) ÷ speed (rpm). Which result should be recorded?

Show answer & explanation

Correct answer: B - 39.3 N·m; the measured test point falls below the torque requirement.

The rest of the C-303 blueprint

The C-303 exam also covers these domains. Drill them in the full free practice test:

That's 10 of 1,030

The full bank has 1,020 more C-303 questions with explanations.

Continue in the free practice test →

View plans